Quadra-Fire 5100I-GD-B Betriebsanleitung Seite 19

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 44
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 18

5100-I ACT WOOD INSERT
R
438-0380E
April 21, 2010
L. Chimney Termination Requirements


Must have an approved and listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
Must be located away from trees or other structures
These are safety requirements and are not meant to assure proper ue draft
NOTE:
Chimney performance may vary.

performance.

overdraft occurs.
M. 2-10-3 Rule
10 ft. (305cm) or more
3 ft. (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
3 in. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
10' (305cm) To Nearest Roofline
2 ft. (61cm)
Flat Roof
Pitched Roof
Figure 19.2
Figure 19.1
Seitenansicht 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 43 44

Kommentare zu diesen Handbüchern

Keine Kommentare